How does the fan tach (FG) signal work?

A fan's tach (FG) output pulses a fixed number of times per shaft revolution — two pulses per revolution is the most common convention, but it is model-specific. The host converts frequency to speed with RPM = 60 × f / PPR. Get the pulses-per-revolution wrong and the displayed speed is off by a whole-number factor — the fan runs fine while the monitoring lies.

The conversion and the classic mismatch

RPM = 60 × f_tach / PPR. Example: a tach at 100 Hz with 2 PPR means 3,000 rpm; the same 100 Hz on a 4 PPR fan means 1,500 rpm. When a replacement fan has different PPR than the incumbent, the host displays double or half the true speed — a pure reporting error that looks exactly like a performance change. Count pulses with a meter for 30 s during qualification and derive PPR empirically; never inherit it from the old part's datasheet.

Tach frequencyPPR = 2PPR = 4PPR = 1
50 Hz1,500 rpm750 rpm3,000 rpm
100 Hz3,000 rpm1,500 rpm6,000 rpm
150 Hz4,500 rpm2,250 rpm9,000 rpm
Verify PPR on a sample with a counter — it is a 30-second test that prevents the most embarrassing monitoring bug in fan swaps.

Electrical interface

Most tach outputs are open-collector or open-drain: the host supplies a pull-up (commonly 10 kΩ to 3.3 V or 5 V) and the fan pulls the line down at each pulse. Check the output's maximum sink current (a strong pull-up can overload it), the host input's logic threshold at your pull-up voltage, and cable length — long unshielded leads pick up noise that shows up as phantom pulses and jumpy RPM readings.

What a healthy tach tells you

Beyond speed display, the tach is a health instrument: a rising speed at constant duty and rail suggests the load is falling or the fan is slipping out of its operating point; a jittery tach at steady command can precede bearing failure; and a dead tach on a spinning fan means a failed output or a wiring fault. Trend tach against duty in your fleet telemetry — deviations from the unit's own baseline are more informative than any absolute threshold.