Why does the replacement fan report a different speed (RPM)?
Three different problems look identical on the host display: a tach scaling mismatch (reporting error, real speed unchanged), a duty-map difference (real speed changed at the same command), or a genuinely different operating speed (real speed changed at the same rail). Diagnose in that order — each has a different fix.
Step 1 — rule out tach scaling
Compute expected RPM independently: count tach pulses with a meter for 30 seconds and convert using RPM = 60 × f / PPR. If the meter and the host disagree, the pulses-per-revolution of the candidate differs from the incumbent — a pure reporting mismatch. Fix by reconfiguring the host's conversion constant, or by selecting a candidate with the same PPR. The fan itself may be running perfectly.
| Symptom | Meter vs host reading | Cause | Fix |
|---|---|---|---|
| RPM looks 2× or ½ | Meter correct, host wrong | PPR differs | Host conversion constant |
| Speed shifts at same duty | Meter matches host | Duty→RPM map differs | Recalibrate control table |
| Speed shifts on rail only | Meter matches host | Load/rail difference | Check system curve & voltage |
Step 2 — compare duty maps
If real speed differs at the same PWM duty, the candidate's duty-to-RPM table differs. Record RPM at 20/50/100% duty on both fans. Options: accept and re-map the host's control table (common and cheap), or request a speed-matched variant from the candidate maker. Do not assume 50% duty means 50% speed on either fan — most maps are monotonic but not linear, and flatten near maximum duty.
- Log duty→RPM at five points on both fans.
- Re-map the host table if the shape is close; re-select if the floor differs.
- Verify minimum-speed behaviour: below some duties many fans stall.
Step 3 — verify the operating point
If the candidate genuinely runs faster on the same rail at full duty, its P-Q curve is higher — which can change noise, and can even mean the incumbent was system-limited rather than speed-limited. Re-check installed flow or thermal result, not just RPM: a faster-spinning fan at the same operating point is not automatically better cooling. The thermal result on the unit is the acceptance criterion.
Send MEGA Tech your airflow and static pressure target, voltage, size limit, control interface, quantity and environment. We reply with a selection proposal and a sample plan — selection by operating condition, samples validated on your unit.