How do I read a fan P-Q curve?

A P-Q curve plots a fan's airflow (Q) against static pressure (P). The two endpoints are easy: maximum flow at zero pressure (free air) and maximum pressure at zero flow. Everything a design review cares about happens between them — especially where the fan curve crosses your enclosure's resistance curve, which is the only operating point the fan will actually settle at.

The four landmarks on the curve

From right to left: the free-air endpoint (maximum flow, zero pressure), the knee where the curve bends upward, the stall or saddle region on some axial fans, and the shut-off endpoint (zero flow, maximum static pressure). Catalogue CFM is always the free-air endpoint — a number the fan can only reach in an empty room, never inside your product.

Where the real operating point comes from

Your enclosure adds a resistance curve that rises roughly with the square of flow: ΔP = K·Q². Draw it on the same axes. The intersection of the fan curve and the system curve is the operating point — the only flow the installation will deliver. If a datasheet claims 100 CFM and your review target is 80 CFM at 0.10 inH₂O, check the intersection, not the headline number.

Point on curveFlowStatic pressureMeaning
Free air100%0 inH₂OUnrestricted test value
Design target≈60–80%system-dependentWhere most products should run
Shut-off0maxBlocked outlet — no cooling
Maximum CFM is a test-lab number. The intersection of the fan curve and your system curve is the only flow your product will see.

Common reading mistakes

Reading one fan curve against several candidate enclosures without re-plotting the system curve each time; comparing fans at free-air flow; ignoring that the curve was measured at a stated density and voltage per test standards such as ISO 5801 or AMCA 210. Curves are measured at fixed voltage (e.g. 12.0 V DC) and stated air density — a hotter, thinner site shifts everything.