What is the difference between dB(A) and sones in fan noise specs?
dB(A) is a logarithmic level; sones are a linear loudness scale. Doubling the sone value means roughly double the perceived loudness, while a 10 dB(A) increase is perceived as roughly a doubling. Fan catalogues use both — always compare within one scale, at the same measurement distance (typically 1 m), and at the same operating point.
The two scales
dB(A) applies an A-weighting curve that mimics human hearing's sensitivity across frequencies, then expresses the result on a logarithmic scale: +3 dB(A) ≈ double the sound power, +10 dB(A) ≈ perceived twice as loud. Sones re-express loudness linearly: 2 sones is twice as loud as 1 sone. A common engineering anchor: 40 dB(A) at 1 m ≈ 1 sone (band-dependent). Because the mapping is frequency-dependent, precise conversion needs spectrum data — approximate for broadband fan noise.
| Change | dB(A) scale | Sone scale |
|---|---|---|
| Perceived twice as loud | +10 dB(A) | ×2 sones |
| Sound power doubled | +3 dB(A) | ×≈1.15–1.3 sones |
| Half as loud | −10 dB(A) | ×0.5 sones |
| 2× vs 4× loudness | +20 dB(A) | ×4 sones |
Why the operating point changes everything
Catalogue noise is measured at a stated condition (commonly free air or a nominal back-pressure at 1 m). At your installed operating point — against real enclosure resistance — the fan may run faster or slower than the catalogue state, and noise follows speed strongly. A fan that wins on the datasheet can lose in the box. For tone-sensitive products, also ask for octave-band data: two fans with equal dB(A) can differ sharply in tonal character, and tonal noise annoys far beyond its level.
- Request noise at a stated pressure, not only free air.
- Ask for octave bands when the product has a human within arm's reach.
- Beware 'quiet' claims at reduced voltage: the same fan at full duty tells the truth.
Practical comparison workflow
Normalize candidates: same scale, same distance, same pressure state. Convert mentally with the anchors above. Then weigh character: a fan 2 dB(A) higher but with no discrete tone usually sounds better than a 'quieter' fan with a strong blade-pass or PWM tone. Validate on the unit — structure-borne transmission through panels can dominate what the customer hears, independent of the fan's airborne number.
Send MEGA Tech your airflow and static pressure target, voltage, size limit, control interface, quantity and environment. We reply with a selection proposal and a sample plan — selection by operating condition, samples validated on your unit.